INFORMATION CENTER · OFFICE DATA CABLING
The Difference Between LSZH and CPR: Checking Labels and Documentation for Office Data Cables
LSZH refers to a "low-smoke, zero-halogen" construction; it does not, by itself, indicate the cable's CPR Euroclass rating. When purchasing office data cables, verify the full product code—along with the jacket specifications and the declared CPR class—and ensure you have the corresponding Declaration of Performance (DoP) for that specific product. Simply seeing "Cat6" or "Cat6A" labeled on a product is not a substitute for this documentation check.

LSZH and CPR: Distinguish cable category, jacket and reaction-to-fire performance
Terms like "Cat6A," "LSZH," and "Dca" found in a quote address different criteria. The category relates to data transmission performance; the jacket description refers to material properties; and the CPR classification pertains to the declared reaction-to-fire performance. Collapsing these into a single "quality score" can obscure discrepancies between the project specifications and the actual items being quoted.
For instance, on the product family page for Nexans’ LANmark-6 U/UTP line, versions with LSZH jackets—rated Eca, Dca, and Cca—are listed as distinct items with separate product codes. This demonstrates that a line item simply labeled “LSZH cable” does not specify which exact product will be delivered. Always rely on the specific product reference (part number) provided in the offer, rather than the general product family name.
LSZH and CPR: Ensure the label matches the documentation for the specific product.
Leviton’s guidance on the Construction Products Regulation (CPR) highlights the importance of the product label and the Declaration of Performance (DoP). When reviewing a purchase record, ensure you have access to the manufacturer’s current technical datasheet and the corresponding DoP. A general brand logo appearing in a sales presentation does not constitute a declaration for a specific reel of cable.
In the example of the CommScope 884050654/16 product datasheet, the LSZH specification is listed in a separate section, while the CPR classification is detailed as Dca s2, d2, a1; a link to the relevant DoP is also provided on the same page. This example applies only to that specific product and should not be interpreted as a universal classification for all CommScope cables. Do not use documentation intended for a different product reference.
A template for recording details during the quotation and delivery phases.
| Check item | Information to be recorded | Action to be taken in case of a discrepancy |
|---|---|---|
| Product identity | Manufacturer, full reference, package label, and document date | Do not accept based solely on a similar family name |
| Jacket and category | List Cat6/Cat6A information and LSZH/PVC designation separately | Clarify any missing information with the supplier |
| Declaration | Euroclass statement, sub-classes (if applicable), and link to the DoP (Declaration of Performance) | Re-verify the document against the product code |
| Project requirement | Specification clause, installation route, and the person responsible for approval | Keep the record open until a compliance decision is reached |
This table is Quad Bilişim’s original procurement record example; it is not a certificate or proof that a regulatory check is complete. If the quoted product code differs from the code on the delivered box, matching cable colors are not enough to close the record. Keep the change justification, equivalence documentation and authorized approval together.
What does this check not replace?
This guide does not prescribe one mandatory fire classification for every office in Türkiye. Qualified project professionals must assess the building use, route, project conditions and applicable requirements. A reaction-to-fire classification is not a guarantee of how long a circuit continues operating during a fire or of the safety of an entire building.
Document verification is not a substitute for data transmission testing of the installed cabling. In addition to procurement and delivery records, data cabling test report and Cat6/Cat6A selection criteria examine these separately. For an office renovation project in Istanbul, including this list in the project scope/survey file makes it easier to track material selection alongside the scope of implementation.
What does NPD mean in a DoP?
NPD (No Performance Determined) in a declaration of performance means that no performance is declared for the characteristic concerned. Do not read it as a failed test for the entire cable or a numerical value of zero; check which row it belongs to.
A document may declare a reaction-to-fire class in one row and show NPD for another characteristic. Do not apply NPD to other rows; a declared class does not mean that the characteristic marked NPD has been measured.
| Document entry | How to record it | What not to conclude |
|---|---|---|
| NPD | Record the characteristic, the exact declaration and the document version together. | NPD is not a zero value or a failed test result. |
| Reaction-to-fire class | Keep the full class with the DoP reference for the same product code. | It does not demonstrate a passed Cat6/Cat6A transmission test. |
| Blank or illegible field | Ask the manufacturer for a legible document covering the product. | Do not fill a blank field with NPD or a pass on your own. |
LSZH and CPR: Example record for a document clarification
DoP reference: [ ] · Version / date: [ ] · Characteristic: [ ] · Declared value: [ ] · Evidence required by the project: [ ] · Clarification request / owner: [ ]
This is an original document-review example from Quad Bilişim; do not alter the manufacturer’s declaration of performance. If the evidence required by the project is missing, keep the issue open for a qualified project lead. This section explains document reading; it does not prescribe one class for every building in Türkiye or establish legal compliance.
Additional primary sources on NPD
Evaluate the office cabling scope through its documentation
Structured cabling service You may share your current plan, cable references, and delivery expectations for this purpose. Contact Quad Bilişim.
Technical resources
- Nexans — LANmark-6 U/UTP product family and part-number variants
- Leviton — CPR-Rated Cable: label and Declaration of Performance
- CommScope — 884050654/16: jacket, classification, and DoP fields
Source verification: November 2, 2026. The evaluation table, procedural steps, and hypothetical examples are original recommendations by Quad Bilişim; they do not constitute a guarantee of price or outcome.